CONSTRUCTION
Conductor: bare copper wires in accordance with the requirements of Class 5 in HD383.
Insulation: compound of PVC of type TI2.
Core code: HD308 standard
Guaina: PVC of type TM2. Grey RAL 7035.
MECHANICAL PROPERTIES
Max tensile strenght: 15 MPa (mobile laying), 50 MPa (fixed laying)
Operating temperature: -15°C · +70°C.
Short Circuit Temperature: max 160°C per 15 seconds.
Bending radius: min 10 per cable diameter (mobile laying); min 4 per cable diameter (fixed laying)
ELECTRICAL PROPERTIES
Rated voltage: 450/750 V
Test Voltage: 2000 V per 15 min.